Spec Sheets

emLITE

Series CTX – Thin Thermoplastic Combo

ILLUMINATION
• Long lasting, efficient ultra bright white LED lamp heads.
• One 1.1 watt white LED per lamphead.
• Unique all-inclusive lamp, reflector and lens assembly.
• Long life ultra-bright, energy efficient Red or Green LED EXIT sign illumination.


ELECTRICAL
AC Operation
• Universal Input 120/277VAC
• Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code
compliance testing.
• 3.6V long life, maintenance-free, rechargeable NiCd battery (EM models only).
• Internal solid-state transfer switch automatically connects the internal battery to LED board for minimum 90-minute emergency illumination.
• Fully automatic solid-state, two rate charger initiates battery charging to recharge a
discharged battery in 24 hours.
DC Operation
• 12-24VDC for Central Storage Battery systems.
• 12-60VDC for POE or DC power distribution systems.


MOUNTING
• Mounting canopy included for top or end mount.
• Universal knockout pattern on back plate for wall mount.


HOUSING
• Specification-grade, low profile thin plastic design.
• Patented, field selectable universal single/double face configuration.
• Injection-molded, engineering grade, 5VA flame retardant, high-impact resistant,
thermoplastic in white or black finish.
• EZ snap-out Chevron directional indicators.
• Remote capacity of up to 2.0 watts available


OPTIONS
• HL: Provides increased center-to-center spacing (2.0W per head).


WARRANTY/LISTING
• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA,
• UL Listed for damp locations (0°C – 50°C).
• Certified to CEC under Title 20 regulations.

Image
Image Image
Spec Sheet

Combo Series

Series CKX – Thin Die-Cast Aluminum Combo

ILLUMINATION
• Ultra bright, energy efficient long life Red or Green LED
• High performance premium grade, ultra bright white LED lamps.
• 3W (1 LED x 3 watts) per head.


ELECTRICAL
AC Operation
• Universal Input 120/277VAC
• Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code
compliance testing.
• 8.4V long life, maintenance-free, rechargeable NiCd battery (EM models only).
• Internal solid-state transfer switch automatically connects the internal battery to LED board for minimum 90-minute emergency illumination.
• Fully automatic solid-state, two rate charger initiates battery charging to recharge a
discharged battery in 24 hours.
DC Operation
• 12-24VDC for Central Storage Battery systems.
• 12-60VDC for POE or DC power distribution systems.


MOUNTING
• Aluminum mounting canopy included for top or end mount.
• Universal K/O pattern on back plate for wall mount.


HOUSING
• First premium grade die-cast combo in the market. Unique new design provides spec grade EXIT sign with LED lamp heads in one low profile housing.
• Premium-grade, aluminum housing (also available in black or white powder-coated finishes).
• Field selectable knockout chevron directional indicators.
• Quick-snap face plate closure.
• Unique design allows double face conversion in the field.


WARRANTY/LISTING
• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes.
• UL Listed for damp locations (0°C – 50°C).
• Certified to CEC under Title 20 Regulations

Image
Image Image
Spec Sheet

Series CLP – Downlight Thermoplastic Combo

ILLUMINATION
• Ultra bright, energy efficient LED emergency lighting.
• High performance linear down light with adjustable angle for optimal lighting.
• Long life, energy efficent Red or Green LED Exit sign illumination


ELECTRICAL
AC Operation
• Universal Input 120/277VAC
• Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code
compliance testing.
• 4.8V long life, maintenance-free, rechargeable NiCd battery (EM models only).
• Internal solid-state transfer switch automatically connects the internal battery to LED board for minimum 90-minute emergency illumination.
• Fully automatic solid-state, two rate charger initiates battery charging to recharge a
discharged battery in 24 hours.
DC Operation
• 12-24VDC for Central Storage Battery systems.
• 12-60VDC for POE or DC power distribution systems.


MOUNTING
• EZ-snap mounting canopy included for top or end mount.
• Universal knockout pattern on back plate for wall mount.


HOUSING
• Injection-molded, engineering grade, 5VA flame retardant, high-impact resistant,
thermoplastic in white or black finish.
• Universal Single/Double Face
• EZ snap-out Chevron directional indicators.
• Adjustable Down Light


OPTIONS
• Self-diagnostic feature performs monthly, biannual, and annual tests to ensure reliable
operation and meet electrical and life safety codes
• Custom: Signs available with requested “special” wording
• DC Operation


WARRANTY/LISTING
• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes.
• UL Listed for damp locations (0°C – 50°C).
• Certified to CED under Title 20 Regulations

Image
Image Image
Spec Sheet

Central Battery Systems

Universal Central Battery – Series CBM

GENERAL DESCRIPTION

  • Computer based, self-testing/self diagnostic emergency lighting equipment operating MOONLITE LED™ fixtures and exit signs with all components addressable and integrated throughout, allowing precise monitoring of unlimited numbers of fixtures in multiple locations.

    Status reports are available on demand from any location via internet through a cloud-based server. A wide range of fixtures with specialized optics is available for interior and exterior applications. Automated diagnostics and fully addressable fixtures combined with easy access to batteries and long lamp life ensure the lowest possible life cycle costs.

CONSTRUCTION & OPERATION

  • Automatic monitoring and self-test diagnostic functions supplied as standard, including battery condition, transfer switch, battery charger and emergency fixture load. Optional network includes addressable fixtures.
  • Data transfer via ethernet through a cloud- based server.
  • All diagnostic data is available via internet based cloud server, with automatic reporting of all central battery systems in multiple buildings.
  • Installations with full network controls allow two-way communication and monitoring via internet of unlimited quantities of central battery panels and fixtures throughout multiple buildings, from any location.Standard display includes multicolor diagnostic status LED and Push to Test switch. Optional LCD display provides full operational data on two-line digital display including battery voltage, charge current, load condition, fault monitor and fault description, panel temperature, charge current, date stamp and other information.
  • Optional installed printer will produce complete status and history reports on demand.
  • Two standard 12V SLA (Sealed Lead Acid) batteries supply a minimum of 90 minutes of emergency power from 100 to 1,000 watts at 24 VDC.
  • Batteries are readily available for commercial distributors and can beremoved and replaced in minutes, without ladders, lifts or special tools.
  • Battery capacity and fixture load combinations can be adjusted to supply emergency power for longer periods, as required.

EMERGENCY LIGHTING FIXTURES

  • All models of MOONLITE LED™ fixtures and exit signs are optionally available with individual IP addresses, allowing monitoring of individual lamps in each fixture, with RS485 (Twisted Pair) network, or optional Power Line communication
  • Specialized optics produce elongated beam patterns which increases spacing and reduces the total number of fixtures required to illuminate the path of egress.
  • A wide range of fixture types and models is available, covering many combinations of interior and exterior lighting requirements, from floor level to ceiling heights of 40 ft or higher. See www.signtexinc.com for details.
  • Guaranteed minimum LED life to 70% output in 50,000 hrs provides lowest life cycle costs over a building lifetime.
  • LED driver circuits are equipped with two independent power inputs, allowing both emergency and optional night (normal-on) lighting operation.
  • More than two lamps are supplied in every fixture, driven via parallel circuits with independent current controllers. This design ensures compliance with NEC Code for emergency lighting, ie failure of any single LED shall not cause failure of any other LED
  • LED exit signs have high brightness and uniformity with power consumption of 2 watts.

Additional Resources

Image
Spec Sheet

Universal Central Battery – Series CBL

Image

CONSTRUCTION & OPERATION

  • Supplies emergency power at 24VDC for 90 minutes to any combination of general lighting luminaires fitted with the Series ELC Emergency Lighting Control, MOONLITE LED emergency lighting fixtures, and exit signs.
  • Up to eight 24V emergency branch circuits with wire size from #18AWG to #8AWG can be installed with 1-hour rated metal jacket type “MC” cable, per NEC 700.9 (d)(1). If required, loads may be rated for Class 2 wiring. Hard conduit Class 1 wiring is not required unless specified by local codes.
  • 120 VAC standard input, optional 277, 347 or 480 VAC.
  • NEMA Type 1, UL 50 steel cabinet for surface or optional recess mount.
  • Four CBL models are offered to supply from 100 to 1,000 watts emergency power. Less than 25 watts power consumption in standby mode.
  • Batteries are readily accessible for inspection and maintenance by facilities personnel, allowing timely replacement when indicated by the diagnostic system.
  • 100 or more emergency lighting fixtures and exit signs may be connected to a single central battery panel.
  • Optional installed printer will produce test reports on demand as required by NFPA 101, Paragraph 7.9.3.1.3 (5).

ELECTRONICS

  • Computer-based, self-test/self-diagnostic functions complywith NFPA Life Safety Code 101 (2012) Paragraph 7.9.3.1.3.
  • Automatic self-testing diagnostics is standard, with multicolor LED status display
  • Optional LCD display with diagnostic control center enables RT Clock to set start time for diagnostic testing as required, to avoid test activation of emergency lighting in dark areas or in sensitive areas when building is occupied. Displays show fault reports, battery charge, voltage and current load, battery temperature, and complete fault history.
  • Optional installed printer enables easy compliance with LSC 101 Paragraph 7.9.3 for written reports. Any LCD display can be printed as required.
  • Optional Branch Circuit Load Monitoring automatically reports current flow on 8 individual branch circuits, reducing troubleshooting of possible locations following a fault report (requires LCD option for display).
  • Standard 24V charging system is computer controlled and optimizes current flow for maximum battery life. Optional fast charger recycles system from complete discharge to full capacity in less than 12 hrs.

CERTIFICATION & CODES

  • Listed under UL Standard 924, and meets applicable requirements of CSA C22.2 No. 141, NFPA 101 Para 7.9.3.1.3, and NEC 700.12 (c).

WARRANTY

  • 3 year total customer satisfaction warranty. For details see product catalog technical data section.
Image

Additional Resources

Spec Sheet

Universal Central Battery – Series LCM

Image

The LCM panel monitors the status of up to nine (9) branch circuits supplying general lighting for egress pathways, and is connected to one or more CBS panels supplying emergency lighting in the same areas, via a 12V normally ON signal. If any monitored circuit breaker is opened or other circuit failure occurs, the 12V signal will turn OFF and the CBS will immediately activate emergency lighting in the area.The LCM enables compliance with NFPA Life Safety Code 101 (2009), Para 7.9.2.3, which states:

The emergency lighting system shall be arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following:

(1) Failure of a public utility or other outside electrical power supply.

(2) Opening of a circuit breaker or fuse.

(3) Manual act(s), including accidental opening of a switch controlling normal lighting facilities.

Each standard LCM panel is typically installed near a lighting panelboard and can monitor up to nine (9) branch circuits. If the circuits to be monitored are located in different panelboard locations, up to (4) LCM panels may be connected to one CBS panel, to monitor a total of up to (36) branch circuits: (4) sets of signal wiring can be installed using conductors of AWG #20- 22 over distances of more than 1,000 feet from LCM to CBS.

If more than (9) circuits are required to be monitored and are located in a single or nearby panelboard, the standard model MASTER LCM may be connected to up to (2) REMOTE LCM panels, each of which can monitor up to (8) circuits. This allows up to (25) circuits to be monitored with only one 12V signal wire connection to the CBS. Optionally, up to (4) REMOTES may be connected to the MASTER, allowing up to (41) branch circuits to be monitored via the same12V connection.

CONSTRUCTION & OPERATION

  • NEMAType 1, UL 50 steel enclosure for surface (wall) mount, optional recess mount.
  • Solid state switches control up to (9) branch circuits.
  • Available Master-Remote options allow monitoring of up to (41) branch circuits via a single low voltage connection to a CBS panel.
  • Upon loss of power from any monitored circuit breaker, a CBS panel will immediately activate emergency lighting.

ELECTRICAL

  • Universal Input 120/ 277 VAC
  • Max 5 watts power consumption in normal mode.
  • Up to nine solid state sensing switches are ULRecognized and rated for continuous duty.
  • The output circuit to a CBS may be installed using #18-22 AWG NEC/ Class 2 wiring.

CODES

  • Operation complies with NFPALife Safety Code 101 (2009), Para 7.9.2.3. when installed with Signtex central battery systems.
Image
Spec Sheet

Emergency Lighting Control

ELC-P6

GENERAL DESCRIPTION

  • ELC converts an LED luminaire to emergency lighting operation, powered from a Signtex central battery system. Constant power output is factory adjustable to optimize emergency illumination level and fixtures may be on, off, switched or dimmed in normal mode without affecting emergency operation. General lighting fixtures with ELC may be combined with MOONLITE LED™ emergency luminaires and exits in the central battery system, as required.
  • Typical applications for Type P6 may include Down Lights, 2 x 2 or 2 x 4 LED flat panel or other lay-in designs, with normal
    power ranging from 10W to 70 watts or more.
  • All Signtex central battery systems Series CBL and CBM include fully automatic self-test, self-diagnostics. Series CBM includes the MARS™ Monitoring and Reporting System which provides cloud-based internet communication and fault reports delivered automatically via email for all components of the emergency system.  

CONSTRUCTION & OPERATION

  • Die cast aluminum enclosure.
  • External mount, factory or field installable on junction box cover.
  • Normal lighting operation is not affected by ELC operation.
  • Compatible with all types of dimming and lighting controls.

ELECTRICAL

  • Input 24 VDC.
  • Constant emergency power output is factory adjustable from 5W to 24W (see option HP).
  • Output voltage auto sensing range up to 41V.
  • Adjustable emergency lumen output allows optimum settings for any fixture to equal or exceed requirements of NEC and NFPA 101 codes for varying mounting heights and other conditions.
  • Available for LED fixtures operating from 5W to 70W or higher in normal mode.

CODES

  • UL Listed in compliance with ULStandard 924 and CAN/ CSA C22.2 No. 141-15 for field or factory installation in Fire and Electrical Enclosure. All Signtex Central Battery Systems and MOONLITE LED emergency fixtures are Listed to ULStandard 924. 
 
Emergency Operation
Output Voltage Range
21-41 VDC
Current Range (Settable)
100-350 mA
Max Power
14W
Image
Field or factory installation in the Fire and Electrical Enclosure of any LED fixture
Image

ELC-P1

GENERAL DESCRIPTION

  • ELC converts an LED luminaire to emergency lighting operation, powered from a Signtex central battery system. Constant power output is factory adjustable to optimize emergency illumination level and fixtures may be on, off, switched or dimmed in normal mode without affecting emergency operation. General lighting fixtures with ELC may be combined with MOONLITE LED™ emergency luminaires and exits in the central battery system, as required.

  • Typical applications for Type P1 may include down lights or other luminaires with limited space available, in normal power range from 10W to 70W.

  • All Signtex central battery systems Series CBS and CBM include fully automatic self-test, self-diagnostics. Series CBM includes the MARS™ Monitoring and Reporting System which provides cloud-based internet communication and fault reports delivered automatically via email for all components of the emergency system.

CONSTRUCTION & OPERATION

  • Factory or field installable in the Fire and Electrical Enclosure of listed fixtures.
  • Normal lighting operation is not affected by ELC operation.
  • Compatible with all types of dimming and lighting controls.

CODES

  • Recognized component in compliance with UL Standard 924 and CSA C22.2 No. 141 for field or factory installation in Fire and Electrical Enclosure. All Signtex Central Battery Systems and MOONLITE LED emergency fixtures are UL Listed to Standard 924.
Emergency Output
Max Output Voltage
41 VDC
Current Range (Settable)
100-350 mA
Max Power
14W
Option HP
Max Output Voltage
24 VDC
Current Range (Settable)
200 mA
Max Power
24W
Image Image

ELC-P2

GENERAL DESCRIPTION

  • ELC converts an LED luminaire to emergency lighting operation, powered from a Signtex central battery system. Constant power output is factory adjustable to optimize emergency illumination level and fixtures may be on, off, switched or dimmed in normal mode without affecting emergency operation. General lighting fixtures with ELC may be combined with MOONLITE LED™ emergency luminaires and exits in the central battery system, as required.
  • Typical applications for Type P2 may include 2 x 2 or 2 x 4 LED flat panel or other lay-in designs, with normal power ranging from 10W to 70 watts or more.
  • All Signtex central battery systems Series CBS and CBM include fully automatic self-test, self-diagnostics. Series CBM includes the MARS™ Monitoring and Reporting System which provides cloud-based internet communication and fault reports delivered automatically via email for all components of the emergency system.

CONSTRUCTION & OPERATION

  • Factory or field installable in the Fire and Electrical Enclosure of listed fixtures.
  • Normal lighting operation is not affected by ELC operation.
  • Compatible with all types of dimming and lighting controls.
  • Standard mount= Hi temp VHB DF tape. Optional flange for screw mount.

ELECTRICAL

  • Input 24 VDC
  • Constant emergency power output is factory adjustable from 5W to 24W.
  • Output voltage auto sensing range up to to 41V.
  • Adjustable emergency lumen output allows optimum settings for any fixture to equal or exceed requirements of NEC and NFPA 101 codes for varying mounting heights and other conditions.
  • Available for LED fixtures operating from 10W to 70W or higher in normal mode.

CODES

  • Recognized component in compliance with UL Standard 924 and CSA C22.2 No. 141 for field or factory installation in Fire and Electrical Enclosure. All Signtex Central Battery Systems and MOONLITE LED emergency fixtures are UL Listed to Standard 924.
Emergency Operation
Max Output Voltage
41 VDC
Current Range (Settable)
100-350 mA
Max Power
14W
Option HP
Max Output Voltage
24 VDC
Current Range (Settable)
200 mA
Max Power
24W
Image Image

Field or factory installation in the
Fire and Electrical Enclosure
of any LED fixture

ELC-P3

GENERAL DESCRIPTION

  • ELC converts an LED luminaire to emergency lighting operation, powered from a Signtex central battery system. Constant power output is factory adjustable to optimize emergency illumination level and fixtures may be on, off, switched or dimmed in normal mode without affecting emergency operation. General lighting fixtures with ELC may be combined with MOONLITE LED™ emergency luminaires and exits in the central battery system, as required.
  • Typical applications for Type P3 may include high-bay high power luminaires with normal power range from 30W to 400W or higher, and AC LED driver output up to 126V.
  • All Signtex central battery systems Series CBS and CBM include fully automatic self-test, self-diagnostics. Series CBM includes the MARS™ Monitoring and Reporting System which provides cloud-based internet communication and fault reports delivered automatically via email for all components of the emergency system. 

CONSTRUCTION & OPERATION

  • Factory or field installable in the Fire and Electrical Enclosure of listed fixtures.
  • Normal lighting operation is not affected by ELC operation.
  • Compatible with all types of dimming and lighting controls.
  • Standard mount= Hi temp VHB DF tape. Optional flange for screw mount.

ELECTRICAL

  • Input 24 VDC.
  • Constant emergency power output is factory adjustable from 5W to 45W.
  • Up to 4 Channel output for operation in luminaires with up to 4 drivers.
  • Input voltage option to 480 VAC.
  • Output voltage auto sensing range from 21V to 126V.
  • Adjustable emergency lumen output allows optimum settings for any fixture to equal or exceed requirements of NEC and NFPA 101 codes for varying mounting heights and other conditions.
  • Available for LED fixtures operating from 30W to 300W or higher in normal mode.

CODES

  • Recognized component in compliance with UL Standard 924 and CSA C22.2 No. 141 for field or factory installation in Fire and Electrical Enclosure. All Signtex Central Battery Systems and MOONLITE LED emergency fixtures are UL Listed to Standard 924.
Emergency Operation
Output Voltage Range
21-126 VDC
Current Range (Settable)
200-1050 mA
Max Power
45W
Image
Field or factory installation in the Fire and Electrical Enclosure of any LED fixture
Image

ELC-P4

GENERAL DESCRIPTION

  • ELC converts an LED luminaire to emergency lighting operation, powered from a Signtex central battery system. Constant power output is factory adjustable to optimize emergency illumination level and fixtures may be on, off, switched or dimmed in normal mode without affecting emergency operation. General lighting fixtures with ELC may be combined with MOONLITE LED™ emergency luminaires and exits in the central battery system, as required.
  • Typical applications for Type P4 may include high- bay luminaires with normal power range from 50W to 300W, and AC LED driver output up to 180V.
  • All Signtex central battery systems Series CBS and CBM include fully automatic self-test, self-diagnostics. Series CBM includes the MARS™ Monitoring and Reporting System which provides cloud-based internet communication and fault reports delivered automatically via email for all components of the emergency system. 

CONSTRUCTION & OPERATION

  • Factory or field installable in the Fire and Electrical Enclosure of listed fixtures. 
  • Normal lighting operation is not affected by ELC operation. 
  • Compatible with all types of dimming and lighting controls.

ELECTRICAL

  • Input 24 VDC.
  • Constant emergency power output is factory adjustable from 15W to 60W.
  • Up to 4 Channel output for operation in luminaires with up to 4 drivers.
  • Input voltage option to 480 VAC.
  • Output voltage auto sensing range up to 180V.
  • Adjustable emergency lumen output allows optimum settings for any fixture to equal or exceed requirements of NEC and NFPA 101 codes for varying mounting heights and other conditions.
  • Available for LED fixtures operating from 50W to 400W or higher in normal mode.

CODES

  • Recognized component in compliance with UL Standard 924 and CSA C22.2 No. 141 for field or factory installation in Fire and Electrical Enclosure. All Signtex Central Battery Systems and MOONLITE LED emergency fixtures are UL Listed to Standard 924.
Emergency Operation
Output Voltage Range
105-180 VDC
Current Range (Settable)
150-1050 mA
Max Power
60W
Image
Field or factory installation in the Fire and Electrical Enclosure of any LED fixture
Image

ELC-P5

GENERAL DESCRIPTION

  • ELC converts an LED luminaire to emergency lighting operation, powered from a Signtex central battery system. Constant power output is factory adjustable to optimize emergency illumination level and fixtures may be on, off, switched or dimmed in normal mode without affecting emergency operation. General lighting fixtures with ELC may be combined with MOONLITE LED™ emergency luminaires and exits in the central battery system, as required.
  • Typical applications for Type P5 may include LED down lights, with normal power ranging from 5W to 70 watts or more.
  • All Signtex central battery systems Series CBL and CBM include fully automatic self-test, self-diagnostics. Series CBM includes the MARS™ Monitoring and Reporting System which provides cloud-based internet communication and fault reports delivered automatically via email for all components of the emergency system.  

CONSTRUCTION & OPERATION

  • Die cast aluminum enclosure.
  • External mount, factory or field installable on junction box cover.
  • Normal lighting operation is not affected by ELC operation.
  • Compatible with all types of dimming and lighting controls.

ELECTRICAL

  • Input 24 VDC.
  • Constant emergency power output is factory adjustable from 5W to 22W (see option HP).
  • Output voltage auto sensing range up to 41V.
  • Adjustable emergency lumen output allows optimum settings for any fixture to equal or exceed requirements of NEC and NFPA 101 codes for varying mounting heights and other conditions.
  • Available for LED fixtures operating from 5W to 70W or higher in normal mode.

CODES

  • UL Listed in compliance with ULStandard 924 and CAN/ CSA C22.2 No. 141-15 for field or factory installation in Fire and Electrical Enclosure. All Signtex Central Battery Systems and MOONLITE LED emergency fixtures are Listed to ULStandard 924. 
 
Emergency Operation
Output Voltage Range
21-41 VDC
Current Range (Settable)
100-350 mA
Max Power
14W
Image
Field or factory installation in the Fire and Electrical Enclosure of any LED fixture
Image

Moonlite™

Series MLD- Recessed Down Light

GENERAL DESCRIPTION

  • With spacing up to 55 ft in 9 ft ceilings, this recessed down light with a 4” trim is our most efficient emergency luminaire; very effective in long corridors, it is inconspicuous and will blend with general lighting fixtures without affecting the appearance of ceiling layouts
  • All MOONLITE fixtures have a dual lighting function, for normal ambient lighting as well as emergency lighting. The night lighting option delivers big power savings, or can act as a low-energy booster for conventional ambient lighting fixtures. The Security Lighting option can be controlled by an internal time clock, photocell, or from a building management system.

CONSTRUCTION

  • Recessed 4” trim ring installation in ceilings, with standard back plate and universal mount bars.
  • High power LEDs and optical lenses produce an optimized elongated pattern along the path of egress.
  • Models available for surface mount & retrofit.
  • Three versions available:
    BB= Unit equipment with self-contained battery
    RE= Remote for connection to Central Battery System
    AC= For connection to AC 120/277 emergency 
    supply.

OPERATION

  • The most cost- effective emergency lighting possible, with extremely low power consumption and lamp life exceeding 50,000 hrs
  • Provides 1 Fc average emergency lighting along the path of egress from standard ceiling heights, with spacing of over 50 ft.
  • Power consumption 8 watts in emergency mode and about 4 watts for night lighting or security mode.
  • When installed for dual mode operation (emergency and night or security lighting), these units provide tremendous energy savings compared to conventional lighting, up to $.50 per sq ft of lit area. See the Signtex cost comparison.

ELECTRONICS

  • Lamps are connected in parallel. If one lamp fails, one or more lamps will continue in operation.
  • Universal 120/277 VAC input for standard battery or AC unit, or 24 VDC input for remote configuration.
  • Power supply delivers regulated current and voltage to LED lamps at optimum levels to maximize lamp life.
  • Automatic battery diagnostics available for all battery models.

PHOTOMETRIC DATA (IES) FILES
(Right click & choose "save as" to download .ies file)

CODES

  • Manufactured and tested to UL Standard 924 and NFPA Life Safety Code 101.
Image Image
Image Image Image

Additional Resources

Spec Sheet

Series MRD – Recessed Down Light for Remodel Work

GENERAL DESCRIPTION

  • This recessed LED down light is designed for lighting retrofit. With spacing up to 55 ft in 9 ft ceilings, this recessed down light with a 4” trim is our most efficient emergency luminaire. Very effective in long corridors, it is inconspicuous and will blend with general lighting fixtures without affecting the appearance of ceiling layouts.
  • All MOONLITE fixtures have a dual lighting function, for normal ambient lighting as well as emergency lighting. The night lighting option delivers big power savings, or can act as a low-energy booster for conventional ambient lighting fixtures.

OPERATION

  • The most cost- effective emergency lighting possible, with extremely low power consumption and lamp life exceeding 50,000 hrs
  • Provides 1 Fc average emergency lighting along the path of egress from standard ceiling heights, with spacing of over 50 ft.
  • Power consumption 8 watts in emergency mode and about 4 watts for night lighting or security mode.
  • When installed for dual mode operation (emergency and night or security lighting), these units provide tremendous energy savings compared to conventional lighting,  up to $.50 per sq ft of lit area. See the Signtex cost comparison.
  • Two versions available:
    BB=Unit equipment with self- contained battery
    RE=Remote for connection to Central Battery System
    AC=Remote for connection to AC 120/277 emergency supply

ELECTRONICS

  • Lamps are connected in parallel. If one lamp fails, one or more lamps will continue in operation.
  • Universal 24 VDC input for remote configuration.
  • LED driver regulates current and voltage to LED lamps at optimum levels to maximize lamp life.

PHOTOMETRIC DATA (IES) FILES
NOTE: Series MRD/MLS share the same IES file as MLD

(Right click & choose "save as" to download .ies file)

CODES

  • Manufactured and tested to UL Standard 924 and NFPA Life Safety Code 101.
Image Image
Image Image

Additional Resources

Spec Sheet

Series MLS- Surface Mount Down Light

GENERAL DESCRIPTION

  • This architectural housing design blends well with any environment. All parts are machined from extruded aluminum and can be custom finished at the factory to match any interior design plan
  • All MOONLITE fixtures have a dual lighting function, for normal ambient lighting as well as emergency lighting. The night lighting option delivers big power savings, or can act as a low-energy booster for conventional ambient lighting fixtures. The Security Lighting option can be controlled by an internal time clock, photocell, or from a building management system.

CONSTRUCTION

  • Housing and canopy plate from rugged extruded aluminum
  • Mounts cleanly with standard back plate to wall or ceiling, or direct to j-box for exposed conduit applications, such as unfinished ceilings.
  • Standard satin white finish; custom paint or satin anodized finishes are also available.
  • High power LEDs and optical lenses produce an optimized elongated pattern along the path of egress.
  • Three versions available:

    BB= Unit equipment with self-contained battery

    RE= Remote for connection to Central Battery System

    AC= For connection to AC 120/277 emergency supply.

OPERATION

  • The most cost- effective emergency lighting possible, with extremely low power consumption and lamp life exceeding 50,000 hrs
  • Provides 1 Fc average emergency lighting along the path of egress from standard ceiling heights, with spacing of over 50 ft.
  • Power consumption 8 watts in emergency mode and about 4 watts for night lighting or security mode.
  • When installed for dual mode operation (emergency and night or security lighting), these units provide tremendous energy savings compared to conventional lighting,  up to $.50 per sq ft of lit area. See the Signtex cost comparison.
  • Optional battery diagnostics available for all models.

ELECTRONICS

  • Lamps are connected in parallel. If one lamp fails, one or more lamps will continue in operation.
  • Universal 120/277 VAC input for standard battery or AC unit, or 24 VDC input for remote configuration.
  • Power supply delivers regulated current and voltage to LED lamps at optimum levels to maximize lamp life.
  • Automatic battery diagnostics available for all battery models.

PHOTOMETRIC DATA (IES) FILES
NOTE: Series  MRD/MLS share the same IES file as MLD

(Right click & choose "save as" to download .ies file)

CODES

  • Manufactured and tested to UL Standard 924 and NFPA Life Safety Code 101.
Image Image
Image Image

Additional Resources

Spec Sheet

Series MLW – Interior Wall Pack

GENERAL DESCRIPTION

  • At only 5” x 5” in width and height and 2” profile depth, this unit is the smallest emergency wall pack available. It has high lighting output, allowing fixture spacing up to 45 ft for 1Fc average illumination along the path of egress. The all-aluminum construction can be custom finished to match any interior.
  • All MOONLITE fixtures have a dual lighting function, for normal ambient lighting as well as emergency lighting. The night lighting option delivers big power savings, or can act as a low-energy booster for conventional ambient lighting fixtures.

CONSTRUCTION  

  • The smallest wall mount emergency light available: overall size 5” x 5” with 2” profile height.
  • Sturdy aluminum housing and molded polycarbonate lens.
  • Recessed 4” trim ring installation in ceilings, with standard back plate and universal mount bars.
  • High power LEDs and optical lenses produce an optimized elongated pattern along the path of egress.
  • Custom finishes available, including brushed aluminum or other anodized finishes.
  • Standard (2 Lamp) and High Power (3 lamp) models available.
  • Three versions available:
    BB= Unit equipment with self-contained battery
    RE= Remote for connection to Central Battery System
    AC= For connection to AC 120/277 emergency 
    supply.

OPERATION 

  • The most cost- effective emergency lighting possible, with extremely low power consumption and lamp life exceeding 50,000 hrs
  • Provides 1 Fc average emergency lighting along the path of egress from standard ceiling heights, with spacing up to 35 ft.
  • Power consumption 8 watts in emergency mode and about 4 watts for night lighting or security mode.
  • When installed for dual mode operation (emergency and night or security lighting), these units provide tremendous energy savings compared to conventional lighting, up to $.50 per sq ft of lit area. See the Signtex cost comparison.
  • Optional battery diagnostics available for all models.

PHOTOMETRIC DATA (IES) FILES
(Right click & choose "save as" to download .ies file)

CODES

  • Manufactured and tested to UL Standard 924 and NFPA Life Safety Code 101.
Image Image
Image Image

Additional Resources

Spec Sheet

Series MOE- Die Cast Wall Pack

GENERAL DESCRIPTION

  • MOE with die cast aluminum housing is designed for exterior use in wet locations but is also often used in interiors with potential hard use situations, such as gymnasiums, or hallways in apartment or condominium complexes.
  • All MOONLITE fixtures have a dual lighting function, for normal ambient lighting as well as emergency lighting. The night lighting option delivers big power savings, or can act as a low-energy booster for conventional ambient lighting fixtures.
  • Three versions available:
    BB= Unit equipment with self-contained battery
    RE= Remote for connection to Central Battery System
    AC= For connection to AC 120/277 emergency 
    supply.

CONSTRUCTION

  • Rugged die cast aluminum housing and molded polycarbonate lens.
  • Smooth curves allow this unit to blend uniformly with any architectural design.
  • Waterproof and suitable for cold installations to -20 degrees
  • The most compact exterior emergency light available, the remote unit has a height of less than 2”: see specifications sheets.
  • Universal mounting pattern.
  • High power LEDs and prismatic lens produce an optimized elongated pattern along the path of egress.
  • Custom finishes available, including brushed aluminum or other baked enamel finishes.

OPERATION

  • The most cost- effective emergency lighting possible, with extremely low power consumption and lamp life exceeding 50,000 hrs
  • Provides 1 Fc average emergency lighting along the path of egress from standard ceiling heights, with spacing up to 40 ft and forward lighting up to 30 ft.
  • Standard models have power consumption 8 watts in emergency mode and about 4 watts for night lighting or security mode.
  • When installed for dual mode operation (emergency and night or security lighting), these units provide tremendous energy savings compared to conventional lighting, up to $.50 per sq ft of lit area. See the Signtex cost comparison.
  • Optional battery diagnostics available for all models.

PHOTOMETRIC DATA (IES) FILES
(Right click & choose "save as" to download .ies file)

Image Image
Image

Additional Resources

Spec Sheet

Series MAE- Architectural Exterior

A dramatic new and compact architectural design, providing powerful emergency and normal lighting for over-door and other exterior locations. 
The lamp housing and canopy are fabricated from extruded aluminum, in
enamel or anodized finishes, with rugged sealed diffuser lens and stainless hardware, for universal wall or ceiling mount.

CONSTRUCTION

• Extremely low profile, formed aluminum housing. Standard finish is white satin paint; custom colors are available, including brushed aluminum anodized finishes.

• Wet location listed IP66.

• Uniform elongated lighting pattern over required path of egress.

• Three versions are available:

BB= Unit equipment with self-contained battery.

RE= Remote for connection to Central Battery System Series CBS or other qualified source 12V- 24 VDC.

AC= Remote for connection to AC 120/277 supply.

ENERGY EFFICIENT OPERATION

 Dual function operation for night or security lighting as well as emergency lighting.

• Very low power consumption in night/ security mode. This unit offers tremendous energy savings when compared to any fluorescent or incandescent lighting systems during night operations.

• Over 50,000 hour lamp life in normal use.

ELECTRONICS

• Lamps are connected in parallel. If one lamp fails, one or more lamps will continue in operation.

• Universal 120/277 VAC input for standard battery or AC unit, or 24 VDC input for remote configuration.

• Power supply delivers regulated current and voltage to LED lamps at optimum levels to maximize lamp life.

• Automatic battery diagnostics available for all battery models.

CODES

• Manufactured and tested to UL Standard 924 and NFPALife Safety Code 101.

WARRANTY

• 5 year total customer satisfaction warranty. For
details see product catalog technical data section.

PHOTOMETRIC DATA (IES) FILES
(Right click & choose "save as" to download .ies file)

Image
Image Image Image
Spec Sheet

Series MUE – Mullion Mount

GENERAL DESCRIPTION

  • Designed specifically to mount directly on extruded structural mullion beams used in typical glass-frontedentrances and other dividing walls. This unique and very low profile fixture will fit directly on to a 2 ½” high surface and provide extremely efficient emergency and general lighting over the path of egress.
  • 10 & 20 watt models available, with 10" & 20" lengths.

CONSTRUCTION

  • Rugged extruded aluminum housing with stainless hardware is corrosion proof.
  • Wet location listed UL 924 and IP66.
  • Uniform, high brightness lighting over the path of 
    egress.
  • Three versions are available:
    RE= Central Battery System Series CBS or other qualified source 12V- 24 VDC.
    BB= Battery backup from Remote Battery Supply Series RPS.
    (MUE10 Only) 
    AC= 120/277 VAC supply.

ENERGY EFFICIENT OPERATION

  • Dual function operation for night as well as emergency lighting.
  • Very low power consumption in night. This unit offers tremendous energy savings when compared to any fluorescent or incandescent lighting systems during night operations.
  • Over 50,000 hour lamp life in normal use.

ELECTRONICS

  • An advanced LED driver module is incorporated in the fixture, allowing dual operation from the Signtex central battery system for both emergency and general lighting.
  • Lamps are connected in parallel-series strings, as required to meet requirements of NEC and Life Safety Codes.
  • Lighting continues even after failure of one lamp or circuit.

CODES

  • Manufactured and tested to UL Standard 924 and NFPA Life Safety Code 101.

PHOTOMETRIC DATA (IES) FILES
(Right click & choose "save as" to download .ies file)

Image Image
Image Image Image
Spec Sheet

Series MHE- High Output

GENERAL DESCRIPTION

  • The Moonlite LED Series MHE high output emergency light is a powerful new addition to the Signtex family of LED emergency luminaires.
  • The MHE produces over 6,000 lumens of light output, providing maximum emergency lighting floor coverage over wide areas at ceiling heights from 10 to 40 feet or more.
  • The MHE’s low- profile recessed or surface mount design matches seamlessly into any architectural or commercial space, and is ideal for retrofit or new applications.

APPLICATIONS

  • Standard Model: Maximum Floor Coverage from Ceiling Heights up to 40 Feet and More
  • Wide Angle Lens Option: Maximum Floor Coverage from a Standard Ceiling Height

CONSTRUCTION

  • LEDs and electronics encased in a UV stabilized, abrasion-resistant polycarbonate lens with an IP67 rated watertight seal.
  • Recessed Mount- faceplate from extruded machined aluminum, available with brushed finish or a variety of satin enamel paint colors.
  • Surface Mount- steel housing with bracket mount locations and multiple knockouts for wiring connection.
  • Composite outdoor rated gasket seal for wet location operations.

ENERGY EFFICIENT OPERATION

  • Dual function operation for night or security lighting as well as emergency lighting.
  • Very low power consumption in night/ security mode. This unit offers tremendous energy savings when compared to any fluorescent or incandescent lighting systems during night operations.
  • Over 50,000 hour lamp life in normal use.

ELECTRONICS

  • Operates with Central Battery System including low voltage normal lighting operation. See CBS data sheet.
  • Lamps are connected in parallel. If one string of lamp fails, one or more strings will continue in operation.
  • Power supply delivers regulated current and voltage to LED lamps at optimum levels to maximize lamp life.
  • LED color temperature 4,700K and CRI of 70. 70% lumen maintenance (L70) at 50,000 hrs.

CODES

  • Central Battery System listed to UL 924 for emergency and normal lighting operation. LED Lamp Assembly ROHS compliant, LM-79 tested, and rated IP67.

PHOTOMETRIC DATA (IES) FILES
(Right click & choose "save as" to download .ies file)

Image
Image

Standard Model
Max Floor Coverage from a High Ceiling

Image

60' x 60' x 35' Ceiling 
1.0 Fc Average
6.67 Max/Min

Wide Angle Lens Option (-WA) 
Max Floor Coverage from a Standard Ceiling

Image

70' x 70' x 20' Ceiling 
1.0 Fc Average
22.5 Max/Min


Additional Resources

Spec Sheet

Series MHW – High Output Wall Mount

A powerful LED fixture designed for interior or exterior wall mount. Dual function operation in either emergency or optional normal on mode, powered from the Signtex Central Battery System at 24VDC.

GENERAL DESCRIPTION

  • The Moonlite LED Series MHW high output emergency light is a powerful new addition to the Signtex family of LED emergency luminaires.
  • The MHW produces over 6,000 lumens of light output, providing maximum emergency lighting floor coverage over wide areas at ceiling heights from 10 to 40 feet or more.

CONSTRUCTION

  • LEDs and electronics encased in a UV stabilized, abrasion-resistant polycarbonate lens with an IP67 rated watertight and dust-proof seal.
  • Surface Enclosed Mount: steel housing with bracket mount locations and multiple knockouts for wiring connection.
  • Wet location standard.
  • 90 degree lighting cut- off.
  • No exposed mounting hardware.

ENERGY EFFICIENT OPERATION

  • Dual function operation for optional normally on night or security lighting as well as emergency lighting.
  • Over 50,000 hour lamp life in normal use.
  • IES photometric data available for all models.
  • Lamp efficacy: 159 lumens/ watt

ELECTRONICS

  • Operates with Central Battery System including optional low voltage normal lighting operation. See CBS data sheet.
  • Lamps are connected in parallel. If one string of lamp fails, one or more strings will continue in operation.
  • Power supply delivers regulated current and voltage to LED lamps at optimum levels to maximize lamp life.
  • LED color temperature 4,700K and CRI of 70. 70% lumen maintenance (L70) at 50,000 hrs.

CODES

  • Central Battery System listed to UL 924 for emergency and normal lighting operation. LED Lamp Assembly ROHS compliant, LM-79 tested, and rated IP67.

PHOTOMETRIC DATA (IES) FILES
Note: MHW share the same IES file as MHE
(Right click & choose "save as" to download .ies file)

Image

CODES

  • Central battery system listed to UL 924. LED Lamp Assembly ROHS compliant, LM-79 tested, and rated IP67.

WARRANTY

  • 3 year total customer satisfaction warranty. For details see product catalog technical data section
Spec Sheet

Series MFP- Floor Proximity

GENERAL DESCRIPTION

  • A low profile and powerful LED recessed fixture for Mounting up to 4 ft from floor level. Dual function operation in either emergency or normal mode, powered from the Signtex central battery system at 24VDC.

CONSTRUCTION

  • Faceplate from solid machined aluminum, available with brushed finish or a variety of satin enamel paint colors.
  • Steel housing with bracket mount locations and multiple knockouts for wiring connection.
  • Composite outdoor rated gasket seal for wet location operations.
  • UV stabilized polycarbonate or acrylic diffuser window 1/8” thick delivers wide beam output.
  • Modular faceplate and lamp housing removes to allow easy access for service. 

OPERATION

  • Operates with Central Battery System including low voltage normal lighting operation. See CBS data sheet.
  • Dual function operation for night or security lighting as well as emergency lighting.
  • Very low power consumption compared to any fluorescent or incandescent lighting systems.
  • Over 50,000 hour lamp life in normal use.

ELECTRONICS

  • Lamps are connected in parallel. If one lamp fails, one or more lamps will continue in operation.
  • 10 watts total system power.
  • -40 o C Standard minimum operating.
  • LED color temperature standard 5300K, available color temperatures 3000K.
  • An advanced LED driver module is incorporated in the fixture, allowing dual operation from either a battery or normally on power source.
  • Lamps are connected in parallel-series strings, as required to meet requirements of NEC and Life Safety Codes. Lighting continues even after failure of one lamp or circuit.

CODES

  • Manufactured and tested to UL Standard 924 and NFPALife Safety Code 101.
PHOTOMETRIC DATA (IES) FILES
(Right click & choose "save as" to download .ies file)
Image Image
Image
Spec Sheet

Builder Series

Series NSF – NEMA 4X Exit Sign

GENERAL DESCRIPTION

  • Ultra-high output LEDs produce brilliant graphic illumination well above code minimums and are available in long lasting Green and Red single or double face configurations. The NSF series is designed for top or end mounting. All models are UL listed for wet locations and food service operations. Meets requirements of UL Standard 924 and NFPA 101 Life Safety Code. Designed and assembled in the USA.

SPECIAL FEATURES
• Dual 120/277 Voltage
• UL listed for Wet Locations (-20°C to 50°C)
• UL certified for use in the food service operations
• IP66 rated for Ingress protection
• Polycarbonate mounting canopy included for top and end mounted fixtures
• Self-Test Diagnostics is standard for central battery models and optional for integral battery models.
• Optional Tamper-proof hardware helps prevent unauthorized access to the unit.

CONSTRUCTION
• Housing is reinforced polycarbonate construction in white or black finish.
• Corrosion-resistant enclosure with one-piece, high impact resistant, UV stabilized polycarbonate lens and molded gasket with stainless steel screws
• Knockout’s provided for conduit feed applications
• Field selectable knockout Chevron directional indicators


ELECTRONICS
• Universal 120/277 VAC input for standard battery or Ac unit or 24 VDC input for remote configuration
• Remotes may be connected to one of the following:
• Series CBS UNIVERSAL CENTRAL BATTERY SYSTEM
• Series MTL MASTER-REMOTE SYSTEM
• Power supply is surge and spike protected, with a low voltage disconnect.
• Automatically performs all tests and visual indications required by UL Standard 924 and NFPA 101.
• 4.8V long-life, maintenance-free rechargeable NiCd battery (EM models only)
• Internal solid-state transfer switch automatically connects the internal battery to LED board for a minimum of 90-minutes of emergency illumination
• Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours


CODES
• Manufactured and tested to UL Standard 924. Conforms to NFPA Life Safety Code 101, NEC, OSHA, state and local codes
• NEMA 4X4X and NSF rated
• Certified to CEC under Title 20 Regulations


WARRANTY
• 5 year total customer satisfaction warranty. For more information, please contact us.

Image Image
Image
Spec Sheet

BPW Series – Wet Polycarbonate Exit Sign

OVERVIEW
Ultra-high output LEDs produce brilliant graphic illumination well above code minimums and are available in long lasting Green and Red single or double face configurations. The BPW series is designed for top or end mounting. All models are UL listed for wet locations. Meets requirements of UL Standard 924 and NFPA 101 Life Safety Code. Designed and assembled in the USA.

SPECIAL FEATURES
• Dual 120/277 Voltage
• UL listed for Wet Locations (-20°C to 50°C)
• Polycarbonate mounting canopy included for top and end mounted fixtures
• Self-Test Diagnostics is standard for central battery models and optional for integral battery models.
• Optional Tamper-proof hardware helps prevent unauthorized access to the unit

CONSTRUCTION
• 5VA flame retardant, UV-stabilized polycarbonate in white, black or gray finish.
• High-impact resistant, UV-stabilized polycarbonate clear lens.
• Corrosion-resistant enclosure with silicone gasket.
• Universal K/O pattern on back plate for wall mount.
• Top and side K/O’s provided for conduit feed applications
• Field selectable knockout Chevron directional indicators


ELECTRONICS
• Universal 120/277 VAC input for standard battery or Ac unit or 24 VDC input for remote configuration
• Remotes may be connected to one of the following:
• Series CBS UNIVERSAL CENTRAL BATTERY SYSTEM
• Series MTL MASTER-REMOTE SYSTEM
• Power supply is surge and spike protected, with a low voltage disconnect.
• Automatically performs all tests and visual indications required by UL Standard 924 and NFPA 101.
• 4.8V long-life, maintenance-free rechargeable NiCd battery (EM models only)
• Internal solid-state transfer switch automatically connects the internal battery to LED board for a minimum of 90-minutes of emergency
illumination
• Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours


CODES
• Manufactured and tested to UL Standard 924. Conforms to NFPA Life Safety Code 101, NEC, OSHA, state and local codes
WARRANTY
• 5 year total customer satisfaction warranty. For more information, please contact us.

Image Image
Series BPW
Spec Sheet

BLD Series – Builder Universal Thermoplastic

GENERAL DESCRIPTION

  • Attractive and easy to install. The BLD Series combines quality LED illumination with contemporary, soft corner styling to complement any application. Precision molded
    housing, backplate and mounting canopy constructed of impact-resistant, flame-retardant, UV stable thermoplastic resists denting, peeling, scratching and
    corrosion with NFPA approved field selectable chevrons. Available in white and black finishes.

SPECIAL FEATURES
• UL94 V-0 flame retardant thermoplastic housing with universal faceplates and mounting canopy.
• Easy to install, snap together construction.
• Constant current LED driver accepts universal 12V- 24VDC supply from the Signtex Central Battery System.
• Less than two watts power consumption.

INSTALLATION
• Simple snap together universal design allows for faceplate and backplate to be fully interchangeable. Mounting canopy is supplied with all signs and snaps into enclosure with two positive locking tabs.
• 20 In³ Junction Box

WARRANTY
• 5 year total customer satisfaction warranty. For more information, please contact us.

Image Image
Image
Spec Sheet

Coverlite

Coverlite – Series CVR AC

Spec Sheet

Coverlite – Series CVL

CONSTRUCTION

  • When AC power fails, the cover doors open instantly and provide emergency lighting to area required, with automatic retraction when AC power is restored.
  • The cover doors may be color matched to any interior finish so when closed in normal mode, the unit is invisible.
  • The doors are driven by a spring and solenoid with magnetic latch, the simplest & most dependable design on the market.
  • Flush- fitting covers composite fiber hinges.
  • No unauthorized access to the lamp heads.
  • Universal Wall or Ceiling Mount.
  • Surface Mount Available

OPERATION

  • Universal 120/277 VAC input via two- wire feed.
  • Auto- battery diagnostics standard.
  • Remote versions of all models are available, to operate from the Signtex 
    Universal Central Battery System.

PHOTOMETRIC DATA (IES) FILES
(Right click & choose "save as" to download .ies file)

CODES

  • Manufactured and tested to UL Standard 924 and NFPA Life Safety Code 101.

How to Order

Example: CVR-75LC-2-RT

CVR OPTIONS & ADDERS
Remote Test PanelRT
Damp LocationDP
Surface Mount*SM
Remote Battery*RB
Custom Exterior FinishCF
  
*Unit Equipment Only
Spec Sheet

Coverlite LED

Coverlite – Series CVL

GENERAL DESCRIPTION

  • The Series CVL delivers very high lumen output with Dual MR16 LED lamps, and remains hidden in normal conditions. It is ideal for locations with high ceilings, or areas requiring longer spacing between fixtures.

CONSTRUCTION

  • Following AC power failure, cover doors open instantly and provide emergency lighting to area required, with automatic retraction when AC power is restored.
  • The cover doors may be color matched to any interior finish so when closed in normal mode, the unit is practically invisible.
  • Battery Diagnostics standard.
  • Universal Wall or Ceiling Mount.
  • The doors are driven by a simple spring and solenoid with magnetic latch, simple and trouble- free.
  • Automatic reset always returns the moving doors to the correct position after adjustments.
  • Flush- fitting covers with internal reflective surfaces are mounted on composite fiber hinges for extreme durability through multiple cycles.
  • No unauthorized access to the lamp heads by vandals.
  • Two versions available:
    - CVLBB= Unit equipment with self-contained battery
    - CVLRE= Remote for connection to Central Battery System
    - CVLAC= 120/ 277 VAC Input
  • The LED lamps remain stationary, protecting hot filaments from damage by vibration.
  • IES photometric data available for all models.
  • Up to 60,000 hr lamp life; typical installations will never require a lamp replacement.
  • Swivel mounted lamp heads are universally adjustable and can be precisely positioned where light is needed.

ELECTRONICS

  • Isolated switch mode power supply with regulated current and voltage output to the lamp load and battery. Universal AC supply 120/277 VAC input via two- wire feed, or 24 VDC input for remote configuration.
  • Low power consumption in standby mode.
  • Automatic control of charge rate for fast charge and maximum battery life

STANDARD DIAGNOSTICS- ALL MODEL

  • An advanced microprocessor monitors all charger functions and battery condition continuously and automatically performs all tests and visual indications required by UL Standard 924.
  • Diagnostic display by multicolor LED or full function alpha- numeric display (remote test panel).

CODES

  • Manufactured and tested to UL Standard 924 and NFPA Life Safety Code 101.

WARRANTY

  • 3 year total customer satisfaction warranty. For details see product catalog technical data section.

PHOTOMETRIC DATA (IES) FILES
(Right click & choose "save as" to download .ies file)

Image
Spec Sheet

LED Exits & Custom Signs

Series RAE – Rapier Accessible Exit

CONSTRUCTION

  • Ultra-slim diecast aluminum LED emergency exit lighting system; the wall mount profile is 1/2" above the surface
  • The diecast outer housing contains a closely fitted acrylic lens. An LED array is recessed into the housing. The assembly is extremely rugged and can withstand severe impact and vibration without damage
  • For even further protection, clear polycarbonate security covers are available

ELECTRONICS

  • Isolated, all solid state power supply with 2-wire universal input from 120 VAC to 277 VAC with precise current and voltage regulation
  • Power supply is surge and spike protected, with a low voltage disconnect
  • The sealed power supply module with optional NICAD battery pack fits inside a standard 4" square deep J-box. AC and DC wiring quickly attached with plug connectors.

CODES

  • Manufactured and tested to UL Standard 924. Conforms to NFPA Life Safety Code 101, UBC and NEC
Image Image
Image
Spec Sheet

Crystal

Series CRX – Chicago Approved Recessed Edgelit Exit

ILLUMINATION
• Ultra-bright, energy efficient, long-lasting white LEDs provide uniform illumination.
• UV stabilized, silk screened acrylic panels provide consistent, uniform illumination.

ELECTRICAL
AC Operation
• Universal Input 120/277VAC
• Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code
compliance testing.
• 4.8V long life, maintenance-free, rechargeable NiCd battery (EM models only).
• Internal solid-state transfer switch automatically connects the internal battery to LED board for minimum 90-minute emergency illumination.
• Fully automatic solid-state, two rate charger initiates battery charging to recharge a
discharged battery in 24 hours.
DC Operation
• 12-24VDC for Central Storage Battery systems.
• 12-60VDC for POE or DC power distribution systems.


MOUNTING
• Compatible with drywall or drop-thru ceiling mount installations.
• Wall mount capability optional


HOUSING
• Premium-grade, die-cast aluminum housing
• Extruded aluminum trim assembly is easily detachable, providing accessibility for service or maintenance. Also available in optional white finish.
• Single or double face configurations.


WARRANTY/LISTING
• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes.
• UL Listed for damp locations (0°C – 50°C).
• Certified to CEC under Title 20 Regulations.
• Meets City of Chicago and plenum requirements.

Image
Image Image
Spec Sheet

Series CLX – Chicago Approved Edgelit Exit

ILLUMINATION
• Ultra-bright, energy efficient, long-lasting white LEDs provide uniform illumination.
• UV stabilized, silk screened acrylic panels provide consistent, uniform illumination.


ELECTRICAL
AC Operation
• Universal Input 120/277VAC
• Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code
compliance testing.
• 4.8V long life, maintenance-free, rechargeable NiCd battery (EM models only).
• Internal solid-state transfer switch automatically connects the internal battery to LED board for minimum 90-minute emergency illumination.
• Fully automatic solid-state, two rate charger initiates battery charging to recharge a
discharged battery in 24 hours.
DC Operation
• 12-24VDC for Central Storage Battery systems.
• 12-60VDC for POE or DC power distribution systems.


MOUNTING
• Die-cast aluminum mounting canopy provided for universal top, end or back mount


HOUSING
• Premium-grade, die-cast aluminum housing (also available in optional white powder-
coated finishes).
• Single or double face configurations.


WARRANTY/LISTING
• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes.
• UL Listed for damp locations (0°C – 50°C).
• Certified to CEC under Title 20 Regulations.
• Meets City of Chicago Requirements.

Image
Image
Spec Sheet

Series ELX – Edgelit Aluminum Exit Sign

ILLUMINATION
• Ultra bright, energy efficient, long life Red or Green LEDs.
• UV-stabilized ultra-clear acrylic edgelit panel provides consistent, uniform illumination.
• Double face utilizes factory installed silver or white myla background panel.


ELECTRICAL
AC Operation
• Universal Input 120/277VAC
• Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code
compliance testing.
• 4.8V long life, maintenance-free, rechargeable NiCd battery (EM models only).
• Internal solid-state transfer switch automatically connects the internal battery to LED board for minimum 90-minute emergency illumination.
• Fully automatic solid-state, two rate charger initiates battery charging to recharge a
discharged battery in 24 hours.
DC Operation
• 12-24VDC for Central Storage Battery systems.
• 12-60VDC for POE or DC power distribution systems.


MOUNTING
• Aluminum mounting canopy included for top, end or back mount.


HOUSING
• Premium-grade, extruded aluminum housing (also available in optional black or white
powder-coated finishes).
• Self-adhesive, field-installed Chevrons and guide template provided.


OPTIONS
• DG: Self-diagnostic feature performs monthly, biannual, and annual tests to ensure reliable operation and meets electrical and life safety codes.
• USA: Substantial transformation assembly in the U.S. complies with “Assembled in the USA” under the Buy American Act.
• SPV: UL Listed for 208/220/240 Volt, 50/60Hz.


WARRANTY / LISTING
• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes.
• UL Listed for damp locations (0°C – 50°C).
• Certified to CEC under Title 20 Regulations

Image
Image
Spec Sheet

Crystal Recessed – Series CRR

CONSTRUCTION

  • Exceptional brightness and uniformity is achieved with the use of diamond polished lenses, very high quality LEDs and balanced optics. Only four LEDs are used per face, resulting in the lowest power consumption of any edge-lit sign.
  • Solid extruded aluminum trim plate, with satin anodized or baked enamel finishes.
  • Multiple mount options available, including a unique “Free Lens” end- mount with no exposed lamp housing, “waterfall”curved lens for wall mount, double pendants for very high ceilings, and other items.
  • Custom metal anodizing, paint finishes and custom graphics available, as well as custom illumination colors for specialty signs.

OPERATION

  • Universal 120/277 VAC input with power consumption from ½ watt to 1 watt per sign.
  • Optional battery diagnostics available for all models.
  • Remote versions of all models are available, to operate from a Signtex 
    Central Battery Systems.

CODES

  • Manufactured and tested to UL Standard 924.minimums. Conforms to NFPA Life Safety Code 101, UBC and NEC

How to Order

Example: CRRBB-1RCBA-NA-T-DG

CRR OPTIONS & ADDERS
Auto Battery DiagnosticsDG
Central Battery InterfaceCBI
Multilite MasterMTL
"Waterfall" Wall Mount ClearWFC
"Waterfall" Wall Mount w/backplateWFB
End Mount (specify left or right)LE/RE
Damp LocationDP
Backplate (single face only)W=white, B=black, M=mirror
End Mount Free Lens (specify left or right)LEF/REF
Dual AC Input RelayDAC
Single Pendant 12"PEN
Double Pendant 12"PEN
Custom Pendant X" LengthPEN-X

Image Image
Spec Sheet

Crystal Surface Mount – Series CRS

CONSTRUCTION

  • The power supply and battery are installed in a standard recessed J-box, resulting in the most compact design for any surface-mount edge lit sign.
  • The extruded aluminum housing and canopy are fitted with a unique “cam-lock” mount which allows universal wall or ceiling mount without special tools or parts.
  • Exceptional brightness and uniformity is achieved with the use of diamond polished lenses, very high quality LEDs and balanced optics. Only four LEDs are used per face, resulting in the lowest power consumption of any edge-lit sign.
  • Solid extruded aluminum trim plate, with satin anodized or baked enamel finishes.
  • Multiple mount options are available, including single or double pendants, special graphics and illumination colors and other items.
  • Custom metal anodizing, paint finishes and custom graphics available, as well as custom illumination colors for specialty signs.

OPERATION

  • Universal 120/277 VAC input with power consumption from ½ watt to 1 watt per sign.
  • Optional battery diagnostics available for all models.
  • Remote versions of all models are available, to operate from a Signtex 
    Central Battery Systems.

CODES

  • Manufactured and tested to UL Standard 924.Conforms to NFPA Life Safety Code 101, UBC and NE

How to Order

Example: CRSBB-1RCBA-NA-TW-DG

CRS OPTIONS & ADDERS
Auto Battery DiagnosticsDG
Central Battery InterfaceCBI
Multilite MasterMTL
End Mount (specify left or right)LE/RE
Damp LocationDP
Pendant Kit (12")PEN
Swing FaceCRSH
Backplate-Mirror Back (single face only)W=white, B=black, M=mirror
Custom Color FinishesCF

Image Image
Spec Sheet

Crystal Series Edge- Lit Custom Mounting Options

Spec Sheet

Crystal Swing Face – Series CRSW

CONSTRUCTION

  • Extruded aluminum housing with Hang Straight Hinge allow for a full 180º range of motion.
  • 1/4’ thick acrylic lens impact & shock resistant.
  • Automatically returns (swings)to original position.
  • Hang Straight Hinge allows for multiple mounting options; ideal for slanted or curved ceilings.
  • Exceptional brightness and uniformity is achieved with the use of diamond polished lenses, very high quality LEDs and balanced optics. Only four LEDs are used per face, resulting in the lowest power consumption of any edge-lit sign.
  • Custom graphics available, as well as custom illumination colors for specialty signs.

OPERATION

  • Universal 120/277 VAC input with power consumption from ½ watt to 1 watt per sign.
  • Optional battery diagnostics available for all models.
  • Remote versions of all models are available, to operate from a Signtex 
    Central Battery Systems.

CODES

  • Manufactured and tested to UL Standard 924. Conforms to NFPA Life Safety Code 101, UBC and NEC

How to Order

Example: CRSWBB-1RCBA-NA-TW-DG

CRSW OPTIONS & ADDERS
Damp LocationDP
Battery DiagnosticsDG
Mirror Lens (SF)M
White Lens (SF)W
Custom Color FinishesCF

Image Image
Image Image

Additional Resources

Spec Sheet

Rapier

Series NYK – NYC Compliant Die-Cast Aluminum Exit

ILLUMINATION
• Ultra bright, energy efficient, long life Red or Green LEDs.
• New York City compliant 8” EXIT letters

ELECTRICAL
AC Operation
• Universal Input 120/277VAC
• Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code
compliance testing.
• 4.8V long life, maintenance-free, rechargeable NiCd battery (EM models only).
• Internal solid-state transfer switch automatically connects the internal battery to LED board for minimum 90-minute emergency illumination.
• Fully automatic solid-state, two rate charger initiates battery charging to recharge a
discharged battery in 24 hours.
DC Operation
• 12-24VDC for Central Storage Battery systems.
• 12-60VDC for POE or DC power distribution systems.


MOUNTING
• Aluminum mounting canopy included for top or end mount.
• Universal knockout pattern on back plate for wall mount.


HOUSING
• Premium-grade, die-cast aluminum housing (also available in optional black or white powder-coated finishes).
• Field selectable knockout Chevron directional indicators.
• Unique design allows double face conversion in the field.
• Quick-snap face plate closure.


OPTIONS
• DG: Self-diagnostic feature performs monthly, biannual, and annual tests to ensure reliable
operation and meets electrical and life safety codes.
• 2C: Dual circuit option on the AC-only unit enables it to be connected to two different (one acting as a back-up to the other) supplies at the same time.


WARRANTY/LISTING
• Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes.
• UL Listed for damp locations (0°C – 50°C).
• Certified to CEC under Title 20 Regulations.

Image
Image
Spec Sheet

Rapier – Series RPRO

CONSTRUCTION

  • Any graphic available (see current list).
  • Ultra thin die cast aluminum housing; just 1/2" thick in single face, & 1” in double face..
  • Cast aluminum housing, with satin anodized or baked enamel finishes available. Can be finished to match any interior.
  • Ultra high output LEDs produce brilliant graphic illumination well above code minimums.
  • Extremely rugged; can withstand severe impact and vibration without damage.
  • For even further protection, clear polycarbonate security covers are available.

OPERATION

  • Universal 120/277 VAC input with power consumption from ½ watt to 1 watt per sign.
  • The complete power supply module with optional NICAD battery pack fits inside a standard 4" square deep J- box.
  • Optional battery diagnostics available for all models.
  • Remote versions of all models are available, to operate from a Signtex 
    Central Battery Systems.

CODES

  • Manufactured and tested to UL Standard 924. Conforms to NFPA Life Safety Code 101, UBC and NEC

How to Order

Example: RPRONB1GBB-TW-"X-RAY IN USE"

RPRO OPTIONS & ADDERS
Auto Battery DiagnosticsDG
Central Battery InterfaceCBI
Multilite MasterMTL
End Mount (specify left or right)LE/RE
Damp LocationDP
Thin Profile Double Face (Red)TDR
Thin Profile Double Face (Green)TDG
Pendant Kit 12"PEN
1/8" Polycarbonate FacePF
Polycarbonate Security CoverPSC
Custom Color FinishesCF
Recess Mount Kit (Standard)RECX
Recess Mount Kit (Remote)RECRX
Dual AC/Input (With Back Box)DAC
DC Input from 12-48VDCDC
Image Image
Image Image

Additional Resources

Spec Sheet

Rapier – Series RPR

CONSTRUCTION

  • Ultra slim profile, with a housing thickness just over 1/2”.
  • Exceptional brightness and uniformity is achieved with only four LEDs per face, resulting in the lowest power consumption of any die cast sign.
  • Solid extruded aluminum canopy plate for top or end mount. Canopy thickness less than ¼”.
  • Multiple mount options are available, including single or double pendants, special graphics, illumination colors and other items.
  • Custom metal anodizing, paint finishes and custom graphics available, as well as custom illumination colors for specialty signs.

OPERATION

  • Universal 120/277 VAC input with power consumption from ½ watt to 1 watt per sign.
  • Optional battery diagnostics available for all models.
  • Remote versions of all models are available, to operate from a Signtex 
    Central Battery Systems.

CODES

  • Manufactured and tested to UL Standard 924. Conforms to NFPA Life Safety Code 101, UBC and NEC

How to Order

Example: RPRNB1GW-TW-DG

RPR OPTIONS & ADDERS
Auto Battery DiagnosticsDG
Central Battery InterfaceCBI
Multilite MasterMTL
End Mount (specify left or right)LE/RE
Damp LocationDP
Thin Profile Double Face (Red)TDR
Thin Profile Double Face (Green)TDG
Pendant Kit 12"PEN
1/8" Polycarbonate FacePF
Polycarbonate Security CoverPSC
Custom Color FinishesCF
Recess Mount Kit (Standard)RECX
Recess Mount Kit (Remote)RECRX
Dual AC/Input (With Back Box)DAC
DC Input from 12-48VDCDC
Image Image
Spec Sheet

Wheelchair Accessible LED Exits

Series CAE – Crystal Accessible Edge Lit Exit

CONSTRUCTION

  • Extruded aluminum LED lamp housing mounts to a form fitting canopy in solid aluminum that contains a "cam lock" device, which is field adjustable for wall or ceiling mount.
  • Standard finishes: satin white and brushed aluminum
  •  Diamond polished acrylic lenses for optimum light transmission, exterior quality and high brightness.

ELECTRONICS

  • Universal 120/ 277 VAC input for standard battery or AC unit, or 24 VDC input for remote configuration
  • Power supply is surge and spike protected, with a low voltage disconnect
  • The complete power supply module wit optional NICAD battery pack is sealed within a phenolic plastic enclosure, which fits inside a standard 4" square deep J- box. AC and DC wiring is quickly attached with plug connectors.

CODES

  • Manufactured and tested to UL Standard 924. Conforms to NFPA Life Safety Code 101, UBC and NEC
Image Image
Image
Spec Sheet

Series CAEFP- Crystal Accessible Exit Master Remote System

Spec Sheet

Series RAE – Rapier Accessible Exit

CONSTRUCTION

  • Ultra-slim diecast aluminum LED emergency exit lighting system; the wall mount profile is 1/2" above the surface
  • The diecast outer housing contains a closely fitted acrylic lens. An LED array is recessed into the housing. The assembly is extremely rugged and can withstand severe impact and vibration without damage
  • For even further protection, clear polycarbonate security covers are available

ELECTRONICS

  • Isolated, all solid state power supply with 2-wire universal input from 120 VAC to 277 VAC with precise current and voltage regulation
  • Power supply is surge and spike protected, with a low voltage disconnect
  • The sealed power supply module with optional NICAD battery pack fits inside a standard 4" square deep J-box. AC and DC wiring quickly attached with plug connectors.

CODES

  • Manufactured and tested to UL Standard 924. Conforms to NFPA Life Safety Code 101, UBC and NEC
Image Image
Image
Spec Sheet

Series RAEFP- Rapier Accessible Exit Master Remote System

Spec Sheet

Series EAE – Emergence Self-luminous Accessible Exit

Spec Sheet

Remote Power Supply

RPS Series for LED

Spec Sheet

Emergence

Emergence Polycarbonate Security Cover – Series PSC

Spec Sheet

Emergence Aluminum Security Housing – Series ASH

Spec Sheet

Emergence Self-Luminous Series EMP

CONSTRUCTION

  • 100 % Reliable: Internally illuminated by sealed tritium gas light sources.
  • Requires no electrical power, wiring or batteries, and no maintenance.
  • Green light output for maximum visibility in dark conditions. No external light or power is required for activation.
  • Lamps guaranteed for up to 20 years of continuous operation.
  • Observation tested for visibility up to 125 ft in complete darkness.
  • Custom graphics available.

OPERATION

  • One- piece flameproof thermoplastic injection molded housing only 1" thick.
  • Universal field adjustable chevron arrows and universal mounting brackets.
  • Standard finishes satin white or black housing, with white lettering and high contrast red, green or black faceplate. Optional finishes include custom colors.
  • No visible mounting hardware.
  • Suitable for use in hazardous atmospheres and wet locations.

CODES

  • Manufactured and tested to UL Standard 924 and Life Safety Code NFPA 101 and National Electrical Code Article 500, Class I and II conditions. Sealed source and device registered with USNRC for distribution to general licensees

How to Order

Example: EMP101GB-PEN

EMP OPTIONS & ADDERS
Canopy Mount KitCAN
Pendant Mount Kit (12")PEN
Polycarbonate Security CoverPSC
Alum Security HousingASH
Alum Security Housing: Double Face Top MT BracketASH2
Recessed Mount KitREC
Image
Image Image
Spec Sheet

Emergence Self-Luminous Series EMA

CONSTRUCTION

  • Internally illuminated by self- luminous tritium gas lamps with guaranteed luminous life up to 20 years, as specified.
  • Observation tested for visibility up to 125 ft in complete darkness.
  • NO electrical connections, NO heat generated, and NO maintenance required for the life specified, up to 20 years. Suitable for use in wet locations.
  • Output at 525 nanometer wavelength (Green)provides maximum visibility in low ambient brightness.
  • No external light required for activation.

OPERATION

  • Double- wall housing of extruded aluminum with minimum wall thickness of .09" (2.3mm). No visible mounting hardware.
  • Standard finishes: satin anodized brushed aluminum (natural), or Black. Optional finishes available in any custom anodized or painted enamel color.
  • Polycarbonate faceplate window of .125 (3 mm) minimum thickness.
  • Universal field adjustable chevron arrows and universal mounting brackets.

CODES

  • Manufactured and tested to UL Standard 924 and Life Safety Code NFPA 101 and National Electrical Code Article 500, Class I and II conditions. Sealed source and device registered with USNRC for distribution to general licensees.

How to Order

Example: EMA101GBA-PEN

EMA OPTIONS & ADDERS
Canopy Mount KitCAN
Pendant Mount Kit (12")PEN
Black or White FinishB or W
Recessed Mount KitREC
Poly Security CoverPSCA
Image
Image Image
Spec Sheet

New York City Approved

Rapier Die Cast Exit (NYC Approved)

Spec Sheet

Crystal Surface Mount Exit (NYC Approved)

Spec Sheet

Crystal Recessed Mount Exit (NYC Approved)

Spec Sheet

Coverlite Recessed Emergency Light (NYC Approved)

Spec Sheet

State of Connecticut

Series CAE – Crystal Accessible Edge Lit Exit

CONSTRUCTION

  • Extruded aluminum LED lamp housing mounts to a form fitting canopy in solid aluminum that contains a "cam lock" device, which is field adjustable for wall or ceiling mount.
  • Standard finishes: satin white and brushed aluminum
  •  Diamond polished acrylic lenses for optimum light transmission, exterior quality and high brightness.

ELECTRONICS

  • Universal 120/ 277 VAC input for standard battery or AC unit, or 24 VDC input for remote configuration
  • Power supply is surge and spike protected, with a low voltage disconnect
  • The complete power supply module wit optional NICAD battery pack is sealed within a phenolic plastic enclosure, which fits inside a standard 4" square deep J- box. AC and DC wiring is quickly attached with plug connectors.

CODES

  • Manufactured and tested to UL Standard 924. Conforms to NFPA Life Safety Code 101, UBC and NEC
Image Image
Image
Spec Sheet

Series RAE – Rapier Accessible Exit

CONSTRUCTION

  • Ultra-slim diecast aluminum LED emergency exit lighting system; the wall mount profile is 1/2" above the surface
  • The diecast outer housing contains a closely fitted acrylic lens. An LED array is recessed into the housing. The assembly is extremely rugged and can withstand severe impact and vibration without damage
  • For even further protection, clear polycarbonate security covers are available

ELECTRONICS

  • Isolated, all solid state power supply with 2-wire universal input from 120 VAC to 277 VAC with precise current and voltage regulation
  • Power supply is surge and spike protected, with a low voltage disconnect
  • The sealed power supply module with optional NICAD battery pack fits inside a standard 4" square deep J-box. AC and DC wiring quickly attached with plug connectors.

CODES

  • Manufactured and tested to UL Standard 924. Conforms to NFPA Life Safety Code 101, UBC and NEC
Image Image
Image
Spec Sheet

Series EAE – Emergence Self-luminous Accessible Exit

Spec Sheet

Atlantic City, NJ

Crystal Surface Mount with 10″ Letters

Spec Sheet

Signtex Warranty

NFPA Excerpts