ELC-P1

GENERAL DESCRIPTION

  • ELC converts an LED luminaire to emergency lighting operation, powered from a Signtex central battery system. Constant power output is factory adjustable to optimize emergency illumination level and fixtures may be on, off, switched or dimmed in normal mode without affecting emergency operation. General lighting fixtures with ELC may be combined with MOONLITE LED™ emergency luminaires and exits in the central battery system, as required.

  • Typical applications for Type P1 may include down lights or other luminaires with limited space available, in normal power range from 10W to 70W.

  • All Signtex central battery systems Series CBS and CBM include fully automatic self-test, self-diagnostics. Series CBM includes the MARS™ Monitoring and Reporting System which provides cloud-based internet communication and fault reports delivered automatically via email for all components of the emergency system.

CONSTRUCTION & OPERATION

  • Factory or field installable in the Fire and Electrical Enclosure of listed fixtures.
  • Normal lighting operation is not affected by ELC operation.
  • Compatible with all types of dimming and lighting controls.

CODES

  • Recognized component in compliance with UL Standard 924 and CSA C22.2 No. 141 for field or factory installation in Fire and Electrical Enclosure. All Signtex Central Battery Systems and MOONLITE LED emergency fixtures are UL Listed to Standard 924.
Emergency Output
Max Output Voltage
41 VDC
Current Range (Settable)
100-350 mA
Max Power
14W
Option HP
Max Output Voltage
24 VDC
Current Range (Settable)
200 mA
Max Power
24W
Image Image